Are you an EPFL student looking for a semester project?
Work with us on data science and visualisation projects, and deploy your project as an app on top of Graph Search.
Impedance estimation is an important tool for grid- converter interaction evaluation. Using existing grid-connected converters for perturbation injection enables grid impedance estimation during operation without additional hardware (namely dedicated perturbation injection equipment). However, such equipment (e.g. converters for PV systems, BESS, EV charging stations...) have limited voltage reserve, leading to reduced perturbation injection capabilities (i.e. perturbation magnitude) with conventional perturbation signals (pseudo-random binary signals or chirp signals). To enhance the perturbation capabilities of those converters, an asymmetric signal is proposed that increases the perturbation magnitude at a maximum operating point. An extension to a wide-bandwidth chirp signal is then presented.
Christophe Ballif, Alessandro Francesco Aldo Virtuani, Hugo James André Quest
, ,