Publication

Kinetic assessment and modeling of an ozonation step for full-scale municipal wastewater treatment: Micropollutant oxidation, by-product formation and disinfection

Résumé

The kinetics of oxidation and disinfection processes during ozonation in a full-scale reactor treating secondary wastewater effluent were investigated for seven ozone doses ranging from 0.21 to 1.24 g O-3 g(-1) dissolved organic carbon (DOG). Substances reacting fast with ozone, such as diclofenac or carbamazepine (k(P,O3) > 10(4) M-1 s(-1)), were eliminated within the gas bubble column, except for the lowest ozone dose of 0.21 g O-3 g(-1) DOG. For this low dose, this could be attributed to short-circuiting within the reactor. Substances with lower ozone reactivity (k(p,O3) < 10(4) M-1 s(-1)) were only fully eliminated for higher ozone doses.

À propos de ce résultat
Cette page est générée automatiquement et peut contenir des informations qui ne sont pas correctes, complètes, à jour ou pertinentes par rapport à votre recherche. Il en va de même pour toutes les autres pages de ce site. Veillez à vérifier les informations auprès des sources officielles de l'EPFL.