This article summarizes the electromagnetic time-reversal (EMTR) technique for fault location, and further numerically validates its effectiveness when the fault impedance is negligible. In addition, a specific EMTR model considering the fault impedance is derived, and the correctness of the model derivation is verified by various calculation methods. Based on this, we found that when the fault impedance is large, the existing EMTR methods might fail to accurately locate the fault. We propose an EMTR method that improves the location effect of high-impedance faults by injecting double-ended signals simultaneously. Theoretical calculations show that this method can achieve an accurate location for high-impedance faults. To further illustrate the effectiveness, the proposed method is compared with the existing EMTR methods and the most commonly used traveling wave-based method using wavelet transform. The simulation results show that the proposed double-ended EMTR method can effectively locate high-impedance faults, and it is more robust against synchronization errors compared with the traveling wave method. In addition, the proposed method does not require the knowledge or a priori guess of the unknown fault impedance.
Marcos Rubinstein, Hamidreza Karami, Rafael Silva Alipio
Drazen Dujic, Seongil Kim, Gabriele Ulissi